Engineering and remote access
3.5 SIMATIC STEP 7
Firmware update to V2.3.0 with UPS Manager
If the UPS Manager was used to update the firmware to V2.3.0 for devices with PROFINET
interface, then the update cannot be successfully completed. In a case such as this, the
device signals a software error using LED 1 (O.K./BAT.). Such a device can be made
operational again by performing an update using the web server, see Firmware update with
web server (Page 135).
Note
Install the current version of the SITOP Managers, before you start the firmware update. The
installation file for the SITOP Manager is available at no charge on the SITOP home page
(http://www.siemens.com/sitop) or directly
(https://support.industry.siemens.com/cs/ww/en/view/109760607).
Note
Do not switch-off the devices during the firmware update.
The files for updating the firmware (firmware updates) are available online under
(http://support.automation.siemens.com/WW/view/en/79207181). Different firmware
updates are offered depending on the amp rating of the SITOP UPS1600.
Note
Observe the compatibility of the firmware!
Other firmware updates are not compatible.
Determine the amp rating of your SITOP UPS1600 and download the appropriate firmware
update.
Note
From device firmware 2.3, a downgrade can be made to version 2.2.3. A downgrade is not
supported for older versions. Information on how to read out the firmware release from the
device is provided in Section Determining the firmware version (Page 135).
Note
"Reset to Factory" function:
All configuration parameters are reset to the default setting; 0.0.0.0 is used for the IP
address. A new IP address must then be assigned, as otherwise a connection will not be able
to be established to the SITOP Manager or the TIA Portal.
Preconditions
• The SITOP UPS1600 has been correctly connected and linked with the PROFINET IO
system.
• PG/PC with STEP 7 is connected with the network.
102