Engineering and remote access
3.11 SNMP Agent
3.11
SNMP Agent
An SNMP agent is integrated in SITOP UPS1600 corresponding to the PROFINET specification.
Via this SNMP agent, a network management system (e.g. SINEMA server) can call up
administrative information about the unit. Corresponding to the SNMPv1/SNMPv2 notation,
this information is summarized in the "system" group
(iso(1).org(3).dod(6).internet(1).mgmt(2).mib-2(1).system(1)).
The following example illustrates the associated nomenclature:
Name
Access
sysDescr
Read
sysObjectID
Read
sysUpTime
Read
sysContact
Read/write
sysName
Read/write
sysLocation
Read/write
sysServices
Read
180
Explanation
A character string with the following content is
used: "[<Supplier>, <Product family>, <Product
name>, <Order number>, <HwVersion>,
<FwVersion>, <Serial number>]"
Object identification of the automation compo-
nent
Time in 1/100 s since switching on
Text identifier of the contact person for this
unit, as well as information to make contact
with this person. Is provided by the network
manager.
A name assigned by the administrator for this
unit
The physical location of this unit. Is provided by
the network manager.
A value, which specifies the set of services that
this unit offers. The value is coded as the sum of
the individual service identifiers.
Default setting
"Siemens, SITOP Power, UPS1600,
6EP4136-3AB00-2AY0, HW: Ver-
sion 7, FW: Version V02.04.00,
SQ6H4BNL7F5G"
".0.0"
-
-
-
-
"76" (application + end-to-end +
internet)
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76