Bosch Access Easy Controller Hardware Manual page 100

Hide thumbs Also See for Access Easy Controller:
Table of Contents

Advertisement

100 en | 4-Reader Boards and 8 Input/8 Output Boards
Reference: JP1, JP2 and JP3
These jumpers are used to set the card address as shown below.
4-reader board
Address
1
2
3
4
Reference: JP2 and JP3
These jumpers control the address setting for the reader ports. JP2 configures addresses for
the first two reader ports, while JP3 configures addresses for the third and fourth readers.
Reference: JP1
Jumper JP1 sets the addresses for the door contacts, request-to exit inputs and door strike
outputs.
Reference: J1 and J2
These jumpers are not in used in the Access Easy Controller application. They are reserved for
future implementation.
Ver 2.0.0 | 2006.07
JP1
JP2
1-2 OUT
1-2 OUT
3-4 OUT
3-4 OUT
5-6 OUT
5-6 OUT
1-2 IN
1-2 OUT
3-4 OUT
3-4 IN
5-6 OUT
5-6 OUT
1-2 OUT
1-2 OUT
3-4 IN
3-4 OUT
5-6 OUT
5-6 IN
1-2 IN
1-2 OUT
3-4 IN
3-4 IN
5-6 OUT
5-6 IN
Hardware Manual
Access Easy Controller
JP3
1-2 IN
3-4 OUT
5-6 OUT
1-2 IN
3-4 IN
5-6 OUT
1-2 IN
3-4 OUT
5-6 IN
1-2 IN
3-4 IN
5-6 IN
Bosch Security Systems

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents