6 MAINTENANCE
⑦ Replace the existing FL.NET module with the new one and set the new FL.NET module's
rotary switches in the same way as you wrote down in Step ①.
⑧ Turn on the power supply of the controller unit. Then, enter the same IP address as you
recorded in Step ④ and send out the parameter values you saved in Step ④, all by using the
S10V FL.NET System.
⑨ Check that all the set parameter values are identical to those that were saved in Step ④.
⑩ Turn off the power supply of the controller unit.
⑪ Remove the RS-232C cable from both the personal computer and LPU module, which were
connected together in Step ③.
⑫ Connect to the new FL.NET module the connecting cables that you removed in Step ⑥.
⑬ Set the LPU module's LADDER and T/M switches in the same way as you wrote down in
Step ②.
⑭ Turn on the power supply of the controller unit and check that the new FL.NET module is
running normally.
Add-on procedure
① Write down, on a piece of paper, the current settings of two switches, labeled LADDER
(toggle switch) and T/M (rotary switch), respectively, that are accessible at the front side of
the LPU module, the one that is installed in the controller unit in which you are adding on a
FL.NET module.
② Ensure that your application system has been shut down. Then, set the LPU module's
LADDER switch in STOP position and turn off the power supply of the controller unit.
③ Mount the add-on FL.NET module in place according to the instructions given under "3.2
Mounting the Module."
④ Set the add-on FL.NET module's rotary switches in such a way that a new module No.
setting, which must be a sub-module No. setting, will not duplicate with the current rotary
switch settings of the existing main FL.NET module.
⑤ Connect the personal computer and the LPU module together with the RS-232C cable.
Then, turn on the power supply of the controller unit and set parameters for the add-on
FL.NET module by using the S10V FL.NET System.
⑥ Turn off the power supply of the controller unit and connect the connecting cables to the add-
on FL.NET module.
⑦ Set the LPU module's LADDER and T/M switches in the same way as you wrote down in
Step ①.
⑧ Remove the RS-232C cable from both the personal computer and LPU module, which were
connected together in Step ⑤.
⑨ Turn on the power supply of the controller unit and check that the add-on FL.NET module is
running normally.
6-4