46
en | System Functions
6.21
Command 960 – Exit from installer's programming mode with
saving the programming data
This command exits from the installer's programming mode with saving the programming
data.
You can exit from installer's programming mode from any location.
Exit from installer's programming mode:
Enter [9 6 0 #] under installer's programming mode.Two beeps sound and system resets
aftersaving the programmed data and returns to the disarmed state. The STAY and
AWAYindicators are deactivated.
6.22
Command 961 – Reset the control panel to factory default
settings
This command resets the control panel to factory default value. Default values are listed
throughtout this guide and in Section 10 Programming sheets on Page 78.
To reset the control panel to factory defaults:
1.
2.
CAUTION!
Only command [9 6 0 #] performed, the reset factory values will be saved.
6.23
Command 962 – Copy the control panel memory to the
programming key
This command copies the control panel memory to the programming key.
To copy the control panel memory to the programming key:
1.
2.
3.
4.
5.
CAUTION!
Failing to exit from Installer's Programming Mode before removing the programming key can
corrupt the programming key.
F.01U.241.127 | V4 | 2011.12
Enter the installer code (the default is 1234 + 958) and press [#] to enter into installer's
programming mode. Two beeps sound and the STAY and AWAY indicators flash on the
remote keypad to indicate you have entered into installer's programming mode. The
keypad displays the data stored in Location 000.
Enter [9 6 1 #]. Two beeps and the system is reset to the factory default values.
Enter the installer code(the default is 1234 + 958)and press [#] to enter into Installer's
Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the
keypad to indicate you have entered into the installer's programming mode. AMAX
keypad displays the data stored in Location 000.
Connect the programming key to the PROGRAMMING KEY pins at the top of the control
panel's PCB.
Enter [9 6 2 #].
Two beeps sound after the control panel memory is successfully copied to the
programming key. A long beep indicates that the programming key is corrupt and must
bere-programmed by input [9 6 2 #].
Enter command [9 6 0 #] to exit from installer's programming mode.
The STAY and the AWAY indicators are extinguished on the keypad to indicate that
thesystem is disarmed.
Remove the programming key from the control panel.