en | System Functions
NOTICE!
You can only reset Alarms Faults or Tamper conditions, when the related contact or function is
idle.
6.8

Initiate a Modem Call

Enter your Code + [7] and press # two beeps sound and the control panel dials the callback
telephone number programmed in Location 154 – 169 in an attempt to connect to the
installer's remote computer.
The remote computer must be running the remote programming software and must be set to
Waiting for an Incoming Call. If no callback telephone number is programmed, entering code
+[7] has no effect.
6.9

Send Test Report

This function allows code holder to send a test report to a Central Monitoring Station (CMS).
1.
6.10

Bypass Zones

This function allows code holders to manually bypassone or more zones before arming the
system in AWAY Mode or STAY Mode. When a zone is bypassed, access is allowed into that
zone when the system is armed without activating an alarm.
The zone should be programmed as bypass zone enable. If the zone is not programmed as
bypass zone, then it cannot be bypassed manually as bypass zone.
For example, you might want to isolate a zone before arming the system because a zone
passive infrared (PIR) detector is activating false alarms or because you need to leave a pet
inside a particular zone while you are away.
Key-switch zone can't be bypassed.
The non-used zone can't be bypassed.
Alarm Zone bypass:
1.
2.
3.
Bypass Steps:
1.
2.
3.
4.
For example:
To manually bypass zones 1,3 and 4, press:
[Code][9][#][1][*][3][*][4] [*][#]
6.11

Show Zone Type

This function allows code holders to see the zone type
F.01U.241.127 | V4 | 2011.12
Enter your code + [8] and press #.
Two beeps sound and a test report is sent.
Zones that have been bypassed will report to CMS at once.
When the zone bypassed is restored, it will send the restore report to CMS immediately.
When the system is disarmed again after arming, the bypassed zones will be restored. It
will send the bypassed restore report to CMS.
Enter your Code + [9] and press [#] . the AWAY and STAY indicators flash.
Enter the number of the zone to be bypassed and press [*]. Repeat Step 2 for each zone
you want to isolate.
To cancel any isolated zone, enter the number of isolated zone and press [*]. Repeat
Step 3 for each zone you have bypassed.
Press [#] to exit.
Installation Manual
AMAX panel 2000 / AMAX panel 2000 EN
Bosch Sicherheitssysteme GmbH