ECC800 Data Center Controller
User Manual

8.1.8.21 How to Set and Add a Rack-mounted HR04A

Prerequisites
Procedure
Step 1 Add a rack-mounted HR04A.
1.
2.
Table 8-15 Adding a rack-mounted air conditioner HR04A
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
Step 2 On the Running Parameters tab page, set smart cooling product running parameters.
1.
Issue 05 (2019-09-16)
One end of the straight-through cable has been connected to the RS485 port on the
Rack-mounted HR04A, and the other end has been connected to the COM port on the
ETH converter.
When connecting devices, you are advised to add devices one by one and ensure that the
view is consistent with the real object. If all devices have been added and powered on,
only the BLINK function of the ETH converter can be used to identify the mapping
between the rack-mounted HR04A and ETH converter.
Log in to the ECC800 WebUI as an administrator.
Add a rack-mounted HR04A.
Parameter
Name
Device attribute
Device type
Connect to
Communications
port
Device address
Click Test Connect to check whether the rack-mounted HR04A connects to the ECC800
properly.
If the rack-mounted HR04A connects to the ECC800 properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the rack-mounted HR04A does not connect to the ECC800 properly, check
whether the cable between the rack-mounted HR04A and the ECC800 is connected
properly, whether the rack-mounted HR04A and ECC800 are running properly, and
whether the input parameters are consistent with the rack-mounted HR04A
parameters.
Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter n_Device name.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Air Conditioner from the drop-down list
box.
Select rack-mounted air conditioner HR04A
from the drop-down list box.
Select ETH Converter n from the drop-down list
box.
Select COM1 from the drop-down list box.
In this example, Device address is set to 1. During
actual configuration, set the device address based
on the actual situation.