ECC800 Data Center Controller
User Manual
3.
Step 2 Set the running parameters and control parameters for the NetCol5000CF_110HALF on the
WebUI.
1.
2.
3.
4.
----End
8.1.8.19 How to Set and Add a NetCol5000CF_110 Parameters (over
Modbus-TCP)?
Prerequisites
One end of the straight-through cable has been connected to the FE port on the
NetCol5000CF_110 main control board, and the other end has been connected to the POE
port on the smart ETH gateway.
Context
The chilled water smart cooling product is displayed as NetCol5000CF_110 on the ECC800
WebUI and the corresponding smart cooling product is NetCol5000-C(065, 080).
Procedure
Step 1 Set the NetCol5000CF_110 monitoring parameters.
1.
2.
3.
Step 2 Set the running parameters and control parameters for the NetCol5000CF_110 on the WebUI.
1.
2.
Issue 05 (2019-09-16)
Choose Settings > Comm Settings > Modbus Settings, set Link mode to Server and
client, and set Server encryption to Enable.
After the parameters are set, the ECC800 can automatically identify the NetCol5000CF_110HALF.
Log in to the ECC800 WebUI as the administrator.
Choose Monitoring > Air Conditioner > NetCol5000CF-110HALF1.
The following describes how to set the NetCol5000CF-110HALF1.
110HALFx in NetCol5000CF_110HALFx is variable and subject to change with the smart cooling
product model and connection sequence. x indicates the smart cooling product connection sequence.
On the Running Parameters tab page, set the smart cooling product running parameters,
temperature and humidity parameters, and alarm parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).
Enter the home page, click Settings, select user name Admin, enter password 000001,
and click Log In. The NetCol5000CF_110 settings page is displayed.
Choose Settings > Comm Settings > IP Settings, set IP assigning mode to Automatic
(DHCP), and click Submit.
Choose Settings > Comm Settings > Modbus Settings, set Link mode to Server and
client, and set Server encryption to Enable.
After the parameters are set, the ECC800 can automatically identify the NetCol5000CF_110.
Log in to the ECC800 WebUI as the administrator.
Choose Monitoring > Cooling > NetCol5000CF-1101.