Huawei ECC800 User Manual page 105

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Table 5-3 Power distribution settings for a general input unit
Path
Monitoring > Power
Distribution > General
Input Unit > Running
Parameters > Power
Distribution Settings
2.
Step 2 Set parameters for power distribution units on the ECC800 WebUI.
1.
2.
3.
Issue 05 (2019-09-16)
Set the parameters for other general input units in the same way or by synchronizing
parameters.
Path: Maintenance > Parameter Sync
(Optional) To modify the branch signal name of the power distribution unit, choose
System Settings > Signal Name Modify and access the Batch Signal Configuration to
modify the name, and then tap Submit.
The following is an example of how to display two branches for power distribution unit
1.
Choose Monitoring > Power Distribution > General Input Unit > Power
Distribution Unit > Display Configuration, select Branch Information Display
corresponding to QF1 and QF2, and then tap Submit.
Configure the power distribution settings for power distribution unit 1.
Copyright © Huawei Technologies Co., Ltd.
Parameter
Defaul
Name
t Value
Rated system
50
frequency
Rated system
380
voltage
Rated system
250
current
System CT ratio
250
Upper load
80
current threshold
Lower load
60
current threshold
5 Power-On Commissioning
Setting
Set based on actual
conditions.
Set based on actual
conditions.
Set based on actual
conditions.
NOTE
Set this parameter to a value
consistent with the information
on the nameplate of the general
input unit. For example, if the
model is NMW-0250 AC, set
Rated system current to 250
A.
Set based on actual
conditions.
For example, if Rated
system current is 250 A, set
System CT ratio to 250.
When the load current
exceeds the preset value, an
alarm is generated.
When the load current
exceeds the preset value, an
alarm is generated.
95