APPENDIX E
APPENDIX E DNPE.1 DNP DEVICE PROFILE
The following table provides a "Device Profile Document" in the standard format defined in the DNP 3.0 Subset Definitions
Document.
Table E–1: DNP V3.00 DEVICE PROFILE (Sheet 1 of 3)
(Also see the IMPLEMENTATION TABLE in the following section)
Vendor Name: General Electric Power Management
Device Name: UR Series Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Binary Counters (Object 20)
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received:
292
Maximum Data Link Re-tries:
Ë
None
Ë

Fixed at 2
Ë
Configurable
Requires Data Link Layer Confirmation:
Ë
Never

Ë
Always
Ë
Sometimes
Ë
Configurable
GE Power Management
Device Function:
Ë
Master
Ë

Slave
Maximum Application Fragment Size (octets):
Transmitted: 240
Received:
2048
Maximum Application Layer Re-tries:
Ë

None
Ë
Configurable
L90 Line Differential Relay