Siemens HiPath 3000 Series Service Documentation page 561

Table of Contents

Advertisement

Nur für den internen Gebrauch
Grounding the system cabinets and possible patch panels
The grounding of the individual
racks must be performed from
the building's potential equaliza-
tion bus in a star configuration.
The grounding of the individual
cabinets in the rack must be per-
formed from the cabinet's poten-
tial equalization bus in a star
configuration.
Figure 4-13
HiPath 3800 - Grounding the Systems and Patch Panels in a 19-Inch Cabinet
A31003-H3590-S100-7-7620, 06/2012
HiPath 3000/5000 V9, Service documentation
To other patch panels S30807-K6143-X (if present)
(A ground conductor is not required for the S
panel S30807-K6143-X.)
HiPath 3800, EC (if present)
Attach to the grill using
cable ties
HiPath 3800, BC
green/yellow
Min. cross-section ≥ 2.5 mm
Installing HiPath 3000
Installing HiPath 3800
Patch Panel
(if present)
for example, patch panel
S30807-K6143-X
Any color, except for green or yellow
to avoid confusion Min. cross-section
≥ 2.5 mm
2
2
Potential equalization bus, in 19" cabinet
for example
inst_h3.fm
patch
0
4-29