Safety configuration
9.8 Configuring Safety Integrated plus (F-PLC)
9.8.5

Checking the PROFIsafe address

Unique PROFIsafe address
To ensure safe communication, unique PROFIsafe addresses are required throughout the
CPU and the network.
For this reason, it is also necessary that you check the settings of the PROFIsafe addresses
carefully.
WARNING
Unique PROFIsafe addresses
You must ensure the unique assignment of the PROFIsafe address throughout the network
and the CPU.
• The fail-safe I/O of PROFIsafe address type 1 is addressed clearly by its fail-safe
destination address.
• The fail-safe destination address of the fail-safe I/O (drive units in this case) must be
unique for the entire fail-safe I/O throughout the network and the CPU (system-wide).
The fail-safe I/O of PROFIsafe address type 2, e.g. modules of the ET 200SP type, must
also be taken into account.
• Note also the corresponding documentation in the TIA Portal online help in the section
"SIMATIC Safety - Configuration and programming".
SIN001
(
During compilation of the safety program, a warning indicates the importance of unique
PROFIsafe addresses:
Creating and checking the safety printout of the PLC
Create the safety printout by right-clicking on "Safety administration" and selecting "Print" in
the shortcut menu.
200
)
SINUMERIK STEP 7 Toolbox V14 SP1
Configuration Manual, 05/2017, A5E41846325