Appendix 2 IEC 60870-5-104 interoperability
Process information in control direction
(Station-specific parameter, mark each Type ID "X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in both
directions.)
<45>:= Single command
<46>:= Double command
<47>:= Regulating step command
<48>:= Set point command, normalized value
<49>:= Set point command, scaled value
<50>:= Set point command, short floating point value
<51> := Bitstring of 32 bit
<58> := Single command with time tag CP56Time2a
<59>:= Double command with time tag CP56Time2a
<60>:= Regulating step command with time tag CP56Time2a
<61>:= Set point command, normalized value with time tag CP56Time2a
<62>:= Set point command, scaled value with time tag CP56Time2a
<63> := Set point command, short floating point value with time tag CP56Time2a
<64> := Bitstring of 32 bit with time tag CP56Time2a
Either the ASDUs of the set <45> – <51> or of the set <58> – <64> are used.
System information in monitor direction
(Station-specific parameter, mark with "X" if used.)
<70> := End of initialization
System information in control direction
(Station-specific parameter, mark each Type ID "X" if it is only used in the
standard direction, "R" if only used in the reverse direction, and "B" if used in both
directions.)
Section 10
C_SC_NA_1
C_DC_NA_1
C_RC_NA_1
C_SE_NA_1
C_SE_NB_1
C_SE_NC_1
C_BO_NA_1
C_SC_TA_1
C_DC_TA_1
C_RC_TA_1
C_SE_TA_1
C_SE_TB_1
C_SE_TC_1
C_BO_TA_1
M_EI_NA_1