Summary of Contents for ABB MicroSCADA Pro SYS 600C

  • Page 1 MicroSCADA Pro SYS 600C 1.92 Product Guide...
  • Page 3: Table Of Contents

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Issued: 27.5.2009 Product Guide Version: C/30.9.2009 Contents: Copyrights ....................5 Introduction ..................... 6 2.1. This manual ................... 6 2.2. Use of symbols ................6 2.3. Abbreviations ................. 6 2.4. Related documents ................ 7 2.5. Document revisions ...............
  • Page 4 MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide Capacity and performance ..............36 7.1. SYS 600C capacity ..............36 7.2. Data logging capacity ..............36 7.3. Process communication capacity ..........37...
  • Page 5: Copyrights

    In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document.
  • Page 6: Introduction

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide Introduction 2.1. This manual This manual provides product information on the Compact System SYS 600C (later referred to as SYS 600C). It gives an overview of the product functionality, key benefits, application areas, technical details, and capacity and performance. 2.2.
  • Page 7: Related Documents

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide Abbreviation Description Personal Computer Adobe Acrobat file format SNMP Simple Network Management Protocol SNTP Simple Network Time Protocol SYS 600 Product name SYS 600C Product name Universal Serial Bus 2.4. Related documents Name of the document Document ID SYS 600C User's Guide...
  • Page 8: Functional Overview

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide Functional overview SYS 600C is a modular and scalable automation system that can be configured and tailored for various applications and needs. This chapter gives an overview of the main functionality. 3.1. Process communication The process communication is used to connect various process devices, such as IEDs, RTUs, PLC, and Meters to SYS 600C.
  • Page 9: Sys 600C Workplaces

    SYS 600C 1.92 Product Guide Protocol Type IEC 60870-5-104 Master and slave IEC 61850-8 Client ANSI X3.28 - AB (ABB) Master RP 570 Master and slave DNP 3.0 (Subset 3) Master and slave Modbus Master and slave OPC DA, A&E Client OPC DA, A&E...
  • Page 10: Event Display

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide Through the process display the user can continuously monitor the process, such as switches and measurements, as well as access the control dialogs to issue commands, set parameters, and so on. C_20090111.png Figure 3.2.2-1 Process Display System Self Supervision The System Self Supervision function shows the status of the various system components...
  • Page 11: Alarm Display

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide as possible. It can also be freely configured to display the information, the layout, and coloring of the events. It is also possible to have predefined filters that can easily be accessed from toolbars and menus.
  • Page 12: Blocking Display

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide C_20090113.png Figure 3.2.4-1 Alarm Display 3.2.5. Blocking Display The blocking display lists all active blockings in the system. The display can also be used to activate new blockings. The following aspects of a signal can be blocked: updating, control, event logging, alarm generation, event printout, and post-processing.
  • Page 13: Trends Display

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide C_20090114.png Figure 3.2.5-1 Blocking Display 3.2.6. Trends Display The trends display is an application that collects data and visualizes the data in a numerical or graphical form. It is used for following up and analyzing data in time frames from minutes to one month.
  • Page 14: Measurement Reports Display

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide C_20090115.png Figure 3.2.6-1 Trends Display 3.2.7. Measurement Reports Display The measurement reports display is an application that collects data and visualizes the data in a numerical or graphical form. The measurement reports display is used to log and report data during longer periods than the Trends Display, and it is dedicated for energy, current, voltage, temperature, and frequency reports.
  • Page 15: User Management

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide C_20090116.png Figure 3.2.7-1 Measurement Reports Display 3.3. User management Users of the system are given access rights according to the needs. The user sessions can be limited in time. The users can be given the right to view, control, or configure the different parts of the system or process.
  • Page 16: Time Synchronization

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide 3.5. Time synchronization SYS 600C can be synchronized by an external GPS clock. This is typically done using SNTP over the local area network or through a serial port using a protocol provided by the clock manufacturer.
  • Page 17: Opc Connectivity

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide The advantage of using data mirroring instead of standard communication, such as IEC 60870-5-104, is that the data mirroring communication is much more efficient and the required engineering work to build up the system is minimal. Several special functions, such as event buffering during communication breaks and handling of hot stand-by configurations, are automatically taken care of.
  • Page 18 MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide • Integrated tools for system engineering, for example expansion of databases, communication system, HSI clients, and users • Support for third-party software and hardware through the use of open interface and communication •...
  • Page 19: Application Areas

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide Application areas 4.1. Overview SYS 600C provides innovative solutions for different tasks and operations in the power automation process, from Communication Gateway functionality to full-fledged redundant control system applications. SYS 600C is a solid-state computer utilizing information distributed in different locations and hence enabled for a large variety of tasks.
  • Page 20: Sys 600C As Communication Gateway

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide 4.2. SYS 600C as Communication Gateway SYS 600C is used for multiple purposes at a substation level. The Communication Gateway function is one of the tasks that can be utilized at the substation level to enable connections to Remote Control Centers (SCADA).
  • Page 21: Sys 600C As Control System Hsi

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide For increased availability, SYS 600C can easily be configured as a redundant Commu- nication Gateway as shown in Figure 4.2-3. C_20090103.bmp Figure 4.2-3 SYS 600C as Redundant Communication Gateway SYS 600C also supports redundant remote communication lines between SYS 600C and Remote Control Center as shown in Figure 4.2-4.
  • Page 22 MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide C_20090105.bmp Figure 4.3-1 SYS 600C as Control System HSI To reduce the number of devices at the substation level, SYS 600C Control System HSI and the Communication Gateway function can be combined in the same computer as shown in Figure 4.3-2.
  • Page 23: Sys 600C As Communication Server

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide C_20090108.bmp Figure 4.3-4 SYS 600C as Control System HSI for RTU 4.4. SYS 600C as Communication Server SYS 600C can function as a powerful Communication Server in medium and large Remote Control Center configurations as well as in large Substation Automation applications.
  • Page 24 MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide C_20090110.bmp Figure 4.4-2 SYS 600C as Communication Servers in a large Substation Automation system By utilizing the SYS 600C Communication Server solution the processing load in the main system servers SYS 600 or SYS 600C is reduced. The Communication Servers are connected to the process devices and provide the main system servers SYS 600 or SYS 600C with process information.
  • Page 25: Product Structure

    The hardware configuration cannot be changed after order (concerning the parts supplied by the ABB product unit). There are no options that can be ordered separately. There are some hardware options that are specified when ordering, but these cannot be changed later on.
  • Page 26: Software Options

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide SYS 600 software The SYS 600 software can be extended or upgraded to new versions. This is done with the normal ordering tool with the upgrade/extension options. SYS 600 Hotfixes and Service Packs can also be freely taken into use. New SYS 600 versions will be available for the SYS 600C hardware for at least 4 years after the hardware delivery.
  • Page 27: Hsi Features

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide Master protocol IEC 61107 (metering) Alpha Meter protocol RCOM Table 5.2.1-2 Slave protocols Slave protocol IEC 60870-5-101, Single or redundant IEC 60870-5-104, Single or redundant DNP 3.0 LAN/WAN DNP 3.0 Serial RP 570/RP 571 F4F Westinghouse, No gateway support Modbus RTU (CPI) 5.2.2.
  • Page 28: System Functions

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide User interface option Description Value Trends Select this option, if you want Yes/No to use the Trend displays in the Workplaces. Event list Select this option, if you want Yes/No to use the event List displays in the Workplaces.
  • Page 29 1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide Table 5.2.3-1 System size parameters System size parameters Description Value Process I/O Number of process objects 1..20 000 connected to the process Gateway functionality (COM 500i) supports maximum 14 000 indications and 14 000 commands configured within SYS 600C.
  • Page 30 MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide System option and interface Description Value Database mirroring HOST This option should be selected, Yes/No if the database mirroring func- tions are used and this system acts as a Host. The Host is the system that provides process data to another system.
  • Page 31: Computer Options

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide System option and interface Description Value OPC DA Client /External This is a DA Client that is 0...4 loosely coupled to the SYS 600 base system and can therefore be installed also in a separate computer.
  • Page 32 MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide Hardware Power Supply: 176 - 264 VAC / 200 - 370 VDC (Single or redundant) Ethernet ports 6 x RJ45 Ethernet ports 2 x RJ45 + 4 x LC Table 5.3-2 Operating systems Operating system Windows XP Professional, English version Windows XP Professional, Chinese version...
  • Page 33: Hardware Characteristics

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide Hardware characteristics 6.1. Hardware The following tables lists the SYS 600C hardware characteristics. Table 6.1-1 Hardware specifications and dimensions Intel® Core 2 Duo 2.2GHz (T7400) Chipset Intel® 82945GM and ICH7R Memory 2GB DDR2 Intel®...
  • Page 34: Emi/Ems And Environmental Standard Compliance

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide 6.2. EMI/EMS and environmental standard compliance The following tables list the EMI/EMS and environmental standard compliance. Table 6.2-1 IEC 61850-3 standard compliance Type test Description Severity level IEC 61000-4-2-2001 Electrostatic Discharge Level 4 -±8KV Contact/±15KV IEC 61000-4-3-2006 Radiated RF Succeptibility Level 3-18V/m, 6 directions...
  • Page 35 1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide Type test Description Severity level IEC 60870-2-1-1995 Voltage Ripple of DC Level VR3- ≤5% IEEE C37.90 Nonoperational Temperature -40°C~+75°C Range IEEE C37.90 Operational Temperature -30°C (Start Up)~+65°C Range Table 6.2-3 Environmental standard compliance Type test Description Severity level...
  • Page 36: Capacity And Performance

    MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide Capacity and performance 7.1. SYS 600C capacity This chapter gives an overview of the capacity of SYS 600C regarding the following functions or aspects: • Number of IEDs that can be connected •...
  • Page 37: Process Communication Capacity

    1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide This corresponds to: • Number of events: 3 000 000 • Number of logged values: 90 000 000 The maximum number of logged values corresponds roughly to 400 measurements sampled every 15 minutes and stored for 1 + 5 years (current year + 5 years of history). 7.3.
  • Page 38 MicroSCADA Pro 1MRS756804 SYS 600C 1.92 Product Guide Nr of IEDs / line Limited mostly by maximum response time Modbus RTU Nr of IEDs Nr of IEDs / line Limited mostly by maximum response time Modbus TCP Nr of IEDs Nr of IEDs / line Limited mostly by maximum response time...
  • Page 39 1MRS756804 MicroSCADA Pro SYS 600C 1.92 Product Guide Function Impact on process com- Comments munication Reports Workpace with - 1% Per Workplace with Measurement data logging Reports with 15 min report Total of 900 objects data logged by Measurement Reports The following list shows some examples when IEDs are connected to SYS 600C with the following Gateway or NCC connections and with Local process database: •...
  • Page 42 Contact us ABB Oy Substation Automation Products P.O. Box 699 FI-65101 VAASA, FINLAND Tel. +358 10 22 11 Fax. +358 10 224 1094 www.abb.com/substationautomation...