Frequency/torque setting by analog
input (terminal 1, 2, 4)
(2) Override function (Pr. 252, Pr. 253)
Forward
Inverter
rotation
STF
SD
10
Override
2
setting
5
Main
(+)
1
speed
(-)
Override connection diagram
200
150
Pr.252
100
Pr.253
50
0
0V
Voltage across terminals 2 and 5
CAUTION
 When the Pr. 73 setting was changed, check the voltage/current input switch setting. Different setting may cause a fault, failure
or malfunction. (Refer to page 291 for setting.)
REMARKS
 The AU signal must be turned ON to use the terminal 4.
 When inputting compensation to multi-speed operation or remote setting, set "1" (compensation made) in Pr. 28 Multi-speed input
compensation selection. (Initial value is "0")
Parameters referred to 
Pr. 28 Multi-speed input compensation selection
Pr. 73 Analog input selection
296
 Use the override function to change the main speed at a fixed ratio.
 Set any of "4, 5, 14, 15" in Pr. 73 to select an override.
 When an override is selected, the terminal 1 or terminal 4 is used for the main speed
setting and the terminal 2 for the override signal. (When the main speed of the
terminal 1 or terminal 4 is not input, compensation made by the terminal 2 becomes
invalid.)
 Using Pr. 252 and Pr. 253, set the override range.
 How to find the set frequency for override
Set frequency (Hz) = Main speed set frequency (Hz) 
Main speed set frequency (Hz): Terminal 1, 4 input, multi-speed setting
Compensation amount (%): Terminal 2 input
Example)When Pr. 73 = "5"
Initial value
(50% to 150%)
2.5V
5V
(5V)
(10V)
Refer to page 172
Refer to page 291
The set frequency changes as shown below according to the
terminal 1 (main speed) and terminal 2 (auxiliary) inputs.
90
60
45
30
15
0
0
2.5
Terminal 1 input voltage (V)
Compensation amount (%)
100(%)
Terminal 2 5VDC
input(150%)
Terminal 2 2.5VDC
input(100%)
Terminal 2 0V
input(50%)
5