3 - Changing parameters and commands

Changing parameters Comply with the following procedure to change one or more parameters:
11 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
IMPORTANT: parameters can be changed with Trip unit in the Local mode and in the
absence of timing alarms
1. select parameter and enter PIN, if required
2. select new value from list or with the aid of page commands
3. select Confirm command if present:
Figure 4
4. When the new value has been selected/confirmed, the menu of the parameter is accessed automatically,
the changed item presents the new value in light blue and a tick to confirm:
Figure 5
Now proceed by confirming the programming (Step 5)
and make further changes (Step 1).
5. Select the arrow at the top left to access the top menu until the Programming page appears:
Figure 6
6. Various commands are enabled in the programming page:
• Confirm to validate the new parameters and conclude the programming procedure
• Abort to interrupt the save data process
• Modify to go back to the menus and change the parameter or others
Figure 7
ABB | SACE Emax 2
or access other parameters
Ekip Touch - Interface and menus
3 - Changing parameters and commands