Setting The Parameters; Modifying A Parameter; Programming The Trip Unit - ABB SACE Emax 2 Series Instructions For Use Manual

Low voltage air circuit-breakers
Table of Contents

Advertisement

4 - Setting the parameters

Modifying a parameter To set a parameter, you need to select it. Selecting a parameter opens the page Modify Parameter.
Programming the trip unit When a parameter is modified, the new value is indicated in the Start menu, and the parameter is associated
10 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
There are two possible types of Modify Parameter page:
• By option: it consists of a list of the values that can be assigned to the parameter.
• By value: graphical page with a bar for assigning the parameter a numerical value within a range..
to a tick symbol.
The menu with submenus and parameters with ticks appears as follows:
Enable
On
Trip enable
On
Function
Step mode
I20 Threshold
0.60In (240A)
Ul Threshold
100% Un (100V)
Figure 6
The ticks indicate that the changes are not effective. In order make a change effective, the trip unit must be
programmed. To program the trip unit, you need to press the key HOME, that opens the page Programming.
Alternatively, you can go up to the higher level menus until the page is displayed.
In the page Programming:
• A list of the changes made is displayed.
• You are asked to confirm, cancel, or modify the settings.
S(V) Protection
Ekip Touch protection trip unit | 4 - Setting the parameters
ABB | SACE Emax 2

Hide quick links:

Advertisement

Table of Contents
loading