2 - Standard Protections

List
The Standard protections available for all Ekip Touch models, are:
Name
Type of protection
L
Overloads with inverse long-time delay
S
Short-circuit with adjustable delay
S2
Short-circuit with adjustable delay
I
(3)
Instantaneous short-circuit
G
Earth fault with adjustable delay
(2)(5)
Instantaneous short-circuit on circuit-
MCR
(4)
breaker closing
Instantaneous short-circuit
2I
programmable
IU
Current unbalance
Neutral
Different protection on neutral phase
T
Abnormal temperatures
Iinst
Instantaneous short-circuit
(1)
Harmonic
Distorted waveforms
distortion
(7)
Hardware Trip
Internal connection errors
Current thresholds
Control thresholds exceeded
(7)
Further details about the protections are given in document 1SDH001330R1002.
(1)
protection cannot be deactivated; its trip parameters are set by ABB and cannot be edited
not available with LSI version of Trip unit
(2)
can be activated with protection MCR = Disable
(3)
(4)
can be activated with protection I = Disable
if the presence of sensor S.G.R. is activated, the submenu of protection G will be replaced by that of protection Gext, in the Advanced
(5)
menu; with Trip unit models Ekip Hi-Touch and Ekip G Hi-Touch, the two protections are available at the same time
Thermal memory available with curve t=k/I
(6)
the protections do not handle the TRIP, just signaling
(7)
15 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
Th-
reshold
; Zone selectivity available with curve t=k; Block configuration available via Ekip Connect
2
Fun-
Time
Additional functions
ction
Thermal memory, Pre-alarm threshold
Trip enable, Zone Selectivity, Thermal
Memory, Startup enable, Lock
Trip Enable, Zone Selectivity, Startup
enable, Lock
Startup enable, Lock
Trip enable, Zone Selectivity, Startup
enable, Locking, Pre-alarm threshold
Monitoring period, Locking
Zone selectivity, activation function and
mode, Delay ON/OFF
Trip enable, Algorithm
Trip enable
Direction of current flow
ABB | SACE Emax 2
ABB | SACE Emax 2
(6)
Protections