ABB SACE Emax 2 Instructions Manual page 34

Emax low voltage air circuit-breakers e1.2-e2.2-e4.2-e6.2
Table of Contents

Advertisement

32 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
Continued from the previous page
Signal
Suggestions
Internal error
Internal error; contact ABB if this typoe of error occurs
Fault with Ekip Com modules: synchronization problem of SNTP
SNTP error
synchronization reference module
Measurement module parameter reading error, contact ABB
Measuring Error
Ethernet
No external cable on one or more Ekip Com modules with Ethernet connection
disconnected
IEEE 1588 synch
Synchronization problem of IEEE 1588 synchronization reference module
Ekip Com module detected with incorrect / not allowed MAC address, contact
MAC Address
ABB.
Ekip Installation
Installation error between HMI and Mainboard, contact ABB
Measuring
Install Measurement module ( Settings-Circuit breaker-Installation-Measuring-
installation
Install ) menu
Install Rating Plug ( Settings-Circuit breaker-Rating Plug-Install menu) and
RatingPlugInstallation
check connection if there are further faults
Maintenance alarm: carry out maintenance and then reset the alarm via Ekip
Maintenance
Connect (see 1SDH001330R1002)
PC Power exceed
The average power limit setting of the Power Controller has been exceeded
Rating plug not present, value or size incompatible with Ekip Touch
Rating plug
parameters
Zone Selectivity
Error in zone selectivity connections (Hardware Selectivity)
Diag
S.G.R. Toroid
Check connection and state of toroid
Fault in connection of sensors to Trip unit; check status of sensors, including
Sensor L1/L2/L3/
external Neutral, or call ABB
Ne
Check current sensors, status of terminal and cables connecting to Ekip Touch
Configuration
TFTP server enabled and/or configuration session open on module Ekip Com
Session
IEC 61850 or Ekip Hub
IMPORTANT! Ignore the message if all the following conditions are
present at the same time:
• Vaux absence
• Absence of Ekip TT/Ekip T&P/Ekip Programming
• Presence of primary current near to self supply powering minimum
value (condition in which the Power LED flashes)
• After having pressed and held the Trip unit test button for at least three
seconds
__logo__note_tab__NOTE: |I|for further confirmation that the alarm is
unwarranted and must therefore be ignored, temporarily power by even only
Software Not
one of these sources and check that the alarm is no longer displayed:|ii|
Compatible
• Vaux (24 VDC) -> K1 K2. For further details, consult page#s#7
• Ekip TT/Ekip T&P/EKIP Programming
If the conditions indicated above are not present, the software versions
between Mainboard and display (Ekip Touch) are not compatible with
each other: to restore compatibility, please contact ABB
NOTE: modification of all parameters is inhibited via display; if
present, protections L, I and Iinst are active and function with the
parameters prior to the alarm (parameters of previous unit are
active if display has been replaced)
CB status
CB state incorrect (esample: current present but CB in open state)
Switchboard Actor
communication
Check configuration and connection of Ekip Link module
Error
Disconnection of Trip coil detected, check functionality
TC disconnected
Check Trip coil, status of the terminal and cables connecting to Ekip Touch
Contact Wear
Make sure that the contacts/poles are in good condition.
ABB | SACE Emax 2
Continued on the next page
Management operations
1 - Ekip Touch maintenance and troubleshooting