5 - Additional functions

Additional functions Ekip T&P, Ekip Programming and Ekip Bluetooth allow the Trip unit to be connected to Ekip Connect

6 - Default parameters

Ekip Dip default parameters The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front
44 | © 2022 ABB | 1SDH000999R0002 - ECN000232533
software and to access parameters and commands that are not directly available from the front interface;
the main ones are:
Name
Description
Function allowing the user to be informed that more than a year has
Maintenance
passed since the last maintenance or that contact wear has increased by
more than 10%
Bus activation so as to communicate with Ekip Link, Ekip Multimeter or
Local Bus
Ekip Signalling 10K modules
Programmable states for monitoring events, to associate with the Ekip
Programmable states
Signalling 10K contacts
Programmable
Commands which activate according to the state of signals or events
Functions
programmable by the user
Configuration of the Power led of the Trip unit and of all modules
Led Alive
connected
Details of these and other parameters are given in manual 1SDH001330R1002.
DIPs (protections, Frequency, Neutral), other via front bus.
Protection/Parameter
L
S
(1)
I
G
(1)
Frequency
Neutral
Hardware Trip
Local Bus
Alive LED
Maintenance
(1)
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG
version.
Value
1 In; 144 s
Off; 0.1 s
4 In
Off; 0.1 s
50 Hz (IEC) / 60 Hz (UL)
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Disabled
Off
Disabled (Power-on LED fixed)
Off
Ekip Dip | 6 - Default parameters
ABB | SACE Emax 2