Initial Configuration; Setting T/H Sensor Parameters - Huawei FusionCol8000-E140 Quick Manual

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E140 Modular Indirect Evaporative
Cooling System
Quick Guide (2021, Ireland)
No.
12

2.4 Initial Configuration

Log in as the admin user (preset password: 000001) when setting initial
parameters.

2.4.1 Setting T/H Sensor Parameters

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
Figure 2-4 T/H Sensor
Step 2 Set Cold aisle sensor 1 to Enable.
Step 3 Set temperature and humidity parameters.
Issue 02 (2023-08-03)
Item
Teamwork control
button
The T/H sensors outside the unit need to be enabled when they are installed;
otherwise, retain the default settings.
This section describes how to enable Cold aisle sensor 1.
NO TE
You are not advised to modify the parameters that are not listed in the following table.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Power-On and Commissioning
Note
indicates that teamwork control is
disabled.
indicates that teamwork control is
enabled and no teamwork control alarm is
generated.
indicates that teamwork control is
enabled and a teamwork control alarm is
generated.
42

Advertisement

Table of Contents
loading

Table of Contents