Huawei FusionCol8000-E140 Quick Manual page 43

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E140 Modular Indirect Evaporative
Cooling System
Quick Guide (2021, Ireland)
Menu
Settings > Quick
Settings > System
Optional Parts
Issue 02 (2023-08-03)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Parameter
Setting Guide
Teamwork
Indicates whether to enable the
Function
teamwork function. If no, the unit
operates independently. If yes, the
unit operates in a team with other
units.
NOTE
Set this parameter based on onsite heat
load distribution.
Networking
Set the networking mode for
mode
teamwork control. The networking
mode selected on the screen must
match the actual networking mode.
Otherwise, the teamwork function is
unavailable.
Number of
Enter the total number of smart
systems in
cooling products in the group.
this group
Number of
Set the number of running units in
running
this group. The value is an integer
systems in
ranging from 1 to the value of
this group
Number of systems in this group.
Teamwork
This parameter can be set to Enable
power limit
or Disable.
function
Cold aisle
You can enable or disable the cold
sensor*
aisle sensors.
NOTE
If a T/H sensor outside the cabinet is
deployed in the cold aisle, enable the T/H
sensor.
Hot aisle
The sensors in hot aisles can be set to
sensor*
Enable or Disable.
NOTE
If a T/H sensor outside the cabinet is
deployed in the hot aisle, enable the T/H
sensor.
Cold aisle
This parameter can be set to Enable
temperature
or Disable.
and humidity
sharing
Hot aisle
This parameter can be set to Enable
temperature
or Disable.
and humidity
sharing
2 Power-On and Commissioning
37