Can Teamwork + Fe Monitoring - Huawei FusionCol8000-E140 Quick Manual

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E140 Modular Indirect Evaporative
Cooling System
Quick Guide (2021, Ireland)
Figure 1-27 Teamwork communications cable and FE monitoring communications
cable
(1) Orange-white
(5) Blue-white
Figure 1-28 RS485 monitoring communications cable
(4) Blue
----End

1.4.5.2 CAN Teamwork + FE Monitoring

Step 1 Connect teamwork and monitoring communications cables.
Networking
Protocol
Description
Issue 02 (2023-08-03)
(2) Orange
(6) Green
NO TE
Crimp only the core wire 4 (blue) and core wires 5 (blue-white) on the RJ45 connector of
the RS485 monitoring communications cable. Do not crimp core wires 1, 2, 3, 6, 7, and 8.
Otherwise, communication interference may occur.
CAN Teamwork
CAN
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
Copyright © Huawei Digital Power Technologies Co., Ltd.
1 System Installation
(3) Green-white
(4) Blue
(7) Brown-white
(8) Brown
(5) Blue-white
FE Monitoring
Modbus-TCP/SNMP
-
30

Advertisement

Table of Contents
loading

Table of Contents