[1] Entering the apportioned electricity energy value from the CSV data at 30-minute intervals
in the energy management block of the AE-200
① Remove the AE-200 cover, and connect an USB memory device.
② Click [Energy Mgmt] - [Energy management list], and select [CSV output].
③ In [Date Range], set the period from the following day of the billing run start or 3 days prior to the current
date, whichever is later (hereinafter referred to as the "start date") to the current date (hereinafter referred
to as the "end date") and touch [CSV output] while [Energy management block] and [30-minute intervals]
are selected.
Open the output CSV file in Microsoft Excel and enter the "apportioned electricity energy" value in the
energy management block unit in the check sheet.
④ Enter the date and time in "Time period" in the CSV file in the start date and end date.
[2] Entering the apportioned electric energy values in the BACnet
®
⑤ Use BACnet
Apportioned Electric Energy" (LOG_01xx83) or "Trend Log Interlocked Units Apportioned Electric Energy"
(LOG_61aa83) objects, and enter the apportioned electricity value at the time 30 minutes after the date/
time entered in the start date column.
"Log_Buffer" value × 0.1 = Apportioned electric energy [kWh]
®
⑥ Use BACnet
Apportioned Electric Energy" (LOG_01xx83) or "Trend Log Interlocked Units Apportioned Electric Energy"
(LOG_61aa83) objects, and enter the apportioned electricity value at the time 30 minutes after the date/
time entered in the end date column. (If the log at the date/time of the end date is not stored, wait for at
least 30 minutes and check again.)
"Log_Buffer" value × 0.1 = Apportioned electric energy [kWh]
[3] Checking the difference value
⑦ Calculate the difference value from the apportioned electric energy values of the start date and the end
date and enter it.
[4] Checking whether the electric energy value is correct
⑧ Check that the difference value of the trend log object matches the apportioned electric energy value of
the CSV output. If there is no problem, insert a check mark in the check box.
WT08246X03
Trial Run Tool and read the "Log_Buffer" property values of the "Trend Log Group
Trial Run Tool and read the "Log_Buffer" property values of the "Trend Log Group