Mitsubishi Electric AE-200A Instruction Book page 21

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Note
For how to operate BACnet
Trial Run Tool–.
Enter the apportioned electric energy value for the representative single air conditioning unit if the group
consists of multiple units. Enter "-" for the air conditioning units other than the representative unit.
The total values may not match completely because the electric energy value is rounded off to one decimal
place.
If a check needs to be performed on the billing run start date, perform a continuous operation of each indoor
unit for at least 2 hours after the apportioned result is stored for the first time after at least 30 minutes have
passed since the billing run start, and then perform the procedure in 4-3-3 "Checking the match with the
CSV data (apportioned results) of the AE-200" by replacing the data as follows.
• Read the both "start date" and "end date" as the billing run start date in ③ .
• For the electric energy value to be entered in the "Apportioned electric energy" in ③ , referring to the
CSV file, total the apportioned electric energy values output at 30-minute intervals in the "Outdoor
units - Apportioned electric energy" and "Indoor units - Apportioned electric energy" columns for each
energy management block in the range of the "Date" from "XX:00 or XX:30 minutes of any hour after
at least 30 minutes have passed since the billing run start (at the time when the apportioned result
is stored for the first time)" to "XX:00 or XX:30 minutes of any hour after a continuous operation has
been performed for at least 2 hours."
• The time to be entered in the "start date" in ④ is "XX:00 or XX:30 minutes of any hour after at least
30 minutes have passed since the billing run start (the time when the apportioned result is stored for
the first time)". The time to be entered in the "end date" is "XX:00 or XX:30 minutes of any hour after
a continuous operation has been performed for at least 2 hours."
CSV data (apportioned results) - Unit address unit
If the energy management block consists of 2 units (1-001 and 1-002) and the "start date" is 2015/4/2 11:30 and
the "end date" is 2015/4/2 12:00, total all apportioned electric energy values enclosed in a red circle.
WT08246X03
®
Trial Run Tool, refer to the AE-200/AE-50/EW-50 Instruction Book –BACnet
21
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ae-200eAe-50aAe-50eEw-50aEw-50e

Table of Contents