Settings and indications
Connections for HMI on Arc Monitor
Display on HMI
Keyboard on HMI
LED signal on HMI
LED signal on Arc Monitor and extension module
configuration switches
Settings (HMI)
Configuration (DIP switches)
Display information
Power supply
Rated supply voltage,U
s
U
variation
s
Rated insulation voltage, U
s
Rated impulse withstand voltage U
Main MCB/fuse
Power cunsumption
Reaction time
From light detection to trip contacts ( K4, K5 ,K6)
From light detection to trip signal relays (K2, K3)
Current condition from input to output
Start-up time
Trip possible
Detector
Maximum length
Service temperature range
Smallest permissible bending radius
Acceptable backlight intensity light without tripping
Optical cable for connecting CSU to an Arc Monitor
Maximum length
s
1 output RJ45 male at front side
1 output RJ14 female at the right side)
52 x 26 mm graphic LCD with LED backlight
Membrane buttons, 4 soft key
Power, Trip, Error
Power, Trip
8 - pole DIP switch on Arc Monitor front
Time and display language
Manual or auto reset of K2 and K3
Use of CSU or not
trip configuration
Trip log, connected modules, actual configuration
self diagnostic test result and error log
100-240 V AC 50-60 Hz
100-250 V DC
AC - 20% - +10%
DC - 25% - + 30%
250 V with reinforced insulation
4 kV
Max. 10 A char. C/fuse 10 A gG
5 W
Approx. 1ms (depends on light intensity)
< 10 ms
<0,4 ms
< 15 ms from power on
30 m with AM and extension - E1
60 m with extension - E3
- 25 to + 70 °C continous
- 25 to + 85 °C short-time
45 mm after installation
10 mm on handling
3000 Lux
30 m
Technical data