Installation
38
1. Connect cable for IRF, K1 to terminal number, 14,12,11.
2. Connect cable for K2 to terminal number 24, 22, 21.
3. Connect cable for K3 to terminal number 34, 32, 31.
4. Connect cable for K4 to terminal number 43, 44.
5. Connect cable for K5 to terminal number 53, 54.
6. Connect cable for K6 to terminal number 63, 64.
Connect Power Supply.
To connect the power supply do the following steps:
1. Connect wires for power supply, use a torque of 0.4 NM.
2. Use screwdriver 2.5 x 0.6 mm (0.98 x 0.23 inches).
3. Cabel area 0.2 - 2.5 mm² (0.078 x 0.98 inch²).
4. Connect the cable for the power supply. 100-240V AC/ 100-250V DC.
14 12 11
24 22 21
34 32 31
43 44
2,5x0,6