Power on to the
Arc Monitor
Checking power
on Arc Monitor
Warning!
Working with high voltage is potentially lethal.
Before switching the power supply on follow the steps below:
1. Check your installation.
2. Check that electrical connections are orderly connected.
3. Check that the configuration is set for your system.
4. Make sure the supply voltage is suitable (100-240V AC/DC 50/60Hz).
5. Make sure you do not leave any working tools in the switching gear.
When the Arc Monitor is connected to supply voltage, then it is on.
When the Arc Monitor is on check the following :
• Green LEDs "Power" on left side of detector inputs is lit.
• Green LED "Power" on HMI is lit.
• HMI is showing text.