Breaker Trip; Dip Switch 3 In Position 0, Dip Switch 4 To Postiotion On - ABB Arc Guard System TVOC-2 Installation And Maintenance Manual

Hide thumbs Also See for Arc Guard System TVOC-2:
Table of Contents

Advertisement

Installation

Breaker trip

DIP switches 3
and 4 to position 0
DIP switch 3 in
position 0, DIP
switch 4 to posti-
otion ON
40
The trip contacts are located on top of the Arc Monitor.
Se figure below.
DIP switches 3 and 4 configure trip contacts, K4, K5 and K6.
All detectors , X1, X2 and X3, operate the trip signal relays K2 and K3.
Adjust the DIP switches to achive the desired breaker configuration K4, K5,
K6.
DIP switches 3 and 4 in position 0 is the default state (factory settings).
• Any detector on X1, X2 or X3 operates trip contacts, K4, K5 and K6.
Set DIP switch 3 to position 0 and DIP switch 4 to position ON.
O
5 6 7 8
1 2
3 4
N
• Detectors X1 operate trip contact K4.
• Detectors X2 operate trip contact K5.
• Detectors X3 operate trip contact K6.
O
1 2
3 4
5 6 7 8
N