iSitePower-M (MAP05A1, MAB05B1)
User Manual
No.
3
4
5
6
7
8
9
7.10.2 Arranging Cables
Check that the cables are correctly connected. Then fasten the cables to the
corresponding cable slots.
Figure 7-21 Cable hole distribution
Issue 02 (2021-12-30)
Check Item
Cable bonding
Grounding
Switch
Short circuit at AC
input and output ports
Unused terminal and
port
Removal wrench
Installation
environment
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Electrical Connection
Expected Result
Cable ties are evenly distributed and no
burr exists.
Power cables, signal cables, and ground
cables are correctly and securely
connected.
The DC SWITCH and all switches
connected to the product are OFF.
The live wire and neutral wire of an AC
power cable is correctly connected.
Unused terminals and ports are locked
by waterproof glands.
The removal wrench is placed in the
original position in the decorative cover.
The installation space is proper, and the
installation environment is clean and
tidy.
78