Mitsubishi Electric MELSEC iQ-R Series User Manual page 78

Devicenet master/slave module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Address
Address
(decimal)
(hexadecimal)
1280 to 1531
0500H to 05FBH
1532
05FCH
1533
05FDH
1534
05FEH
1535
05FFH
1536
0600H
1537
0601H
1538 to 1549
0602H to 060DH
1550
060EH
1551
060FH
1552 to 1567
0610H to 061FH
1568 to 1572
0620H to 0624H
1573
0625H
1574
0626H
1575 to 1581
0627H to 062DH
1582
062EH
1583
062FH
1584
0630H
1585
0631H
1586
0632H
1587
0633H
1588
0634H
1589 to 1791
0635H to 06FFH
1792 to 2047
0700H to 07FFH
2048 to 2303
0800H to 08FFH
2304 to 2559
0900H to 09FFH
2560 to 2815
0A00H to 0AFFH
2816 to 2879
0B00H to 0B3FH
2880 to 3071
0B40H to 0BFFH
3072 to 3135
0C00H to 0C3FH
APPX
76
Appendix 3 Buffer Memory
Name
Description
Master function I/O
Stores the start addresses and sizes (in
address
increments of words) of the master function
receive data (address: 0700H to 07FFH) and
master function transmit data (address: 0900H to
09FFH) used by each slave node.
Current link scan time
Stores the current link scan time. (Unit: ms)
Minimum link scan time
Stores the minimum link scan time after power-on.
(Unit: ms)
Maximum link scan time
Stores the maximum link scan time after power-
on. (Unit: ms)
System area
Slave function
Stores the I/O communication status of the slave
communication status
function.
Slave function error
Stores the communication error code occurred in
information
the slave function.
System area
Slave function receive
Sets the I/O data receive size of the slave
*1
size setting
function.
Slave function transmit
Sets the I/O data transmit size of the slave
*1
size setting
function.
System area
Model display
Stores "RJ71DN91" in the ASCII code.
Node address
Stores the current operating node address.
Mode switch number
Stores the current operating mode switch number.
System area
Hardware test item
Stores the current executing test item number at
display
the hardware test and communication test.
Hardware test result
Stores the results of the hardware test and
area
communication test.
Parameter save/clear
Selects whether to save or clear the parameter
selection bit
with 'Request for saving/clearing parameters to
Flash ROM' (Y17).
Auto communication
Sets whether to start the I/O communication
*1
start setting
automatically with the parameter saved in the
flash ROM when the CPU module is reset or
powered off and on.
Operation setting for bus
Sets whether to reset the CAN chip
off error area
(communication chip) of the RJ71DN91 to restart
the communication when a bus off error occurs.
The communication can be restarted even when a
value is changed after a bus off error occurs.
Data consistency setting
Sets whether to enable or disable the data
consistency for refresh or the data consistency
dedicated instruction.
Data consistency setting
Stores the enabled/disabled state of data
status
consistency for refresh or the data consistency
dedicated instruction.
System area
Master function receive
Stores the data received from each slave node.
data
System area
Master function transmit
Sets the data to be transmitted to each slave
data
node.
System area
Slave function receive
Stores the data received from the master node.
data
System area
Slave function transmit
Sets the data to be transmitted to the master
data
node.
As
As
Read, write
master
slave
function
function
Read
Read
Read
Read
Read
Read
Read, write
Read, write
Read
Read
Read
At hardware test
Read
At hardware test
Read
Read, write
Read, write
Read, write
Read, write
Read
Read
Write
Read
Write

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-rj71dn91

Table of Contents