When parameter check abnormally completes
'Module READY' (X0F)
'I/O communication request' (Y11)
'I/O communicating' (X01)
'Master function error set signal'
(X03)
(1) Parameter check
• Even though 'I/O communication request' (Y11) is turned on while 'Auto configuration request' (Y15) or
'Request for saving/clearing parameters to Flash ROM' (Y17) is on, 'I/O communicating' (X01) does not turn
on. After the output signal turns off, turn off and on 'I/O communication request' (Y11) again.
• To stop the I/O communication, set 'I/O communication request' (Y11) and reset it after 200ms or longer.
■When starting the I/O communication automatically at power-on
For auto communication, set 'Auto communication start setting' (Un\G1585) to "Start".
• When the power is turned on, 'Module READY' (X0F) turns on and the parameter is checked.
• When the parameter check normally completes, the I/O communication with each slave node starts and 'I/O
communicating' (X01) turns on.
• When the parameter check abnormally completes, the ERR LED turns on and 'Master function error set signal' (X03) turns
on. 'I/O communicating' (X01) does not turn on at this time. For details on 'Master function error set signal' (X03), refer to
the following.
Page 67 For master function error (X03), (Y13)
• When 'I/O communication signal request' (Y11) is turned on and off, the I/O communication with each slave node stops and
'I/O communicating' (X01) turns off.
When parameter check normally completes
'Module READY' (X0F)
'I/O communicating' (X01)
(1) Parameter check
When parameter check abnormally completes
'Module READY' (X0F)
'I/O communicating' (X01)
'Master function error set signal'
(X03)
(1) Parameter check
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
(1)
ON
(1)
ON
(1)
APPX
71
Appendix 2 I/O Signals
A