Reset

CPU module
SET
Y12
X02 X05
(1) Message communication command
(2) Message communication result
(3) Attribute
 Set the command data in 'Message communication command' (Un\G272 to Un\G287) (0110H to 011FH).
 When 'Message communication request' (Y12) is turned on, the master node transmits a reset message to the slave node set with the command data.
 When the message communication processing completes, the processing result is stored in 'Message communication result' (Un\G288 to Un\G303) (0120H
to 012FH) and 'Message communication completion' (X02) turns on.
 When the message communication processing completes with an error, 'Message communication error signal' (X05) turns on. The content of 'Message
communication result' (Un\G288 to Un\G303) (0120H to 012FH) is read, and the cause of the error is checked.
1 FUNCTIONS
28
1.2 Master Function (Message Communication)
0110H
Ò
T0
011FH
Ó
0120H
Õ
FROM
012FH
Message communication
completion
RJ71DN91
(1)
Message communication
request
(2)
Slave node (MAC ID)
Class
Ó
Instance
(3)
(3)
Instance
(3)
Ô