2. OPERATION PRINCIPLES
Failed Tap-UP:
This state shows that the tap increase operation has failed. The DTR system changes to the Manual state,
independently of the state previous to the Tap-up attempt.
11. Successful Tap-Down:
This state shows that the tap decrease operation has been successful. The DTR system returns to the initial state,
previous to the tap decrease, either Manual or Automatic.
12. Failed Tap-Down:
This state shows that the tap decrease operation has failed. The DTR system changes to the Manual state,
independently of the state previous to the Tap-down attempt.

2.1.4 EXCESSIVE OPERATIONS BLOCK.

This function allows the user to limit the number of raising/lowering tap operations over the OLTC. The user can set
this function for maintenance purposes.
When the DTR is in automatic mode, and the maximum number of allowed operations is exceeded, it will change to
Manual mode. This function can be disabled by setting the Maximum number of operations to zero.

2.1.5 SUCCESSIVE OPERATIONS IN A CERTAIN TIME FRAME BLOCK

This function allows the user to limit the number of raising / lowering tap operations in a specified time interval.
When the regulator is in Automatic Mode and there are continuous operations at a higher speed than the one
specified by Number of Successive Operations and Time window settings, the DTR will change to Manual mode.
Once this function is enabled, it will disable itself after a certain time without operations over the OLTC.
This function can be disabled by setting the Number of Successive Operations to zero.

2.1.6 OVERVOLTAGE, UNDERVOLTAGE AND OVERCURRENT BLOCKS.

When the DTR is in automatic mode, before performing any operation over the OLTC, it checks that the voltage
levels are within the limits specified by Overvoltage and Undervoltage settings. It also checks that the measured
current is lower than Overcurrent setting. In order to enable control over different operations when in MANUAL
mode independently from the protection element blocks, the relay incorporates three settings: BLOQ. M. OVER_V,
BLOQ. M. UNDER_V y BLOQ. M. OVER_I, which allow to consider or not the block condition.

2.1.7 QUICK LOWERING FUNCTION

If the measured voltage exceeds the value set for Quick Lowering, Then the Operating Time becomes 0 s, and
therefore the lowering tap operation is instantaneous.
12
DTR Digital Tap Changer Controller
GE—106305A