Forced fan function
This function operates fan of CHILLER to remove
accumulated snow on the fan.
Snow accumulation prevention, which operates
occasionally when outdoor temperature is below
5°C (41°F), is basic function Use this function by
module control or external contact when the snow
is actually accumulated on the fan only.
The factory default setting for initial entry is module
control. Extra setting is necessary to use external
contact.
Forced pump function
Only pump can be operated while the product is not
operating.
This function is available when using main control.
Refer to page 59 for trial operation for each unit.
Pump operation output
Electric switch for pump is field supply, and not
included in the product. Install interlock circuit
according to electrical wiring diagram when installing
the switch.
Connecting module control
Refer to page 30 for wiring of module control.
84
English
Remote control wiring
For the remote control circuit (including the module
control), use the cord or vinyl sheath cable (0.75-1.25 mm
that meets the local power line requirements.
CAUTION
To prevent error, maintain strong cables, such as
power cable and voltage input cable, and weak
cables, such as module control power cable,
separately.