Periodic Maintenance - Samsung AG010KSV Series Installation Manual

Dvm chiller
Table of Contents

Advertisement

Maintenance

Periodic maintenance

For proper operation, check and record the following list periodically. Recommended values are normal operation
range. Operation time is 3650 hours/year.
Common items
Name
Compressor
Fan
Fan motor
Air side heat
exchanger
Water side heat
maintenance
exchanger
Electronic
expansion valve
High pressure
switch
Electronic valve
Electric switch
Visual check
Visual check
PCB
Inverter
Visual check
Resistance
Thermistor
Visual check
80
English
Periodic maintenance
Checklist
Check standard
Insulation
resistance
Operating
Within standard value
current
Exterior
No crack and noise
Insulation
resistance
Operating
Within standard value
current
Exterior
Water
Within standard value (Refer to page
standard
Check
No malfunction and deformation
operation
Check
Operate in set value
operation
Insulation
Check
No malfunction
operation
No malfunction and deformation
Check
No malfunction
operation
No loosen terminal
No expansion, discoloration, and
leakage of condenser
Should be rated resistance value
value
No deformation
Over 1 MΩ
Over 1 MΩ
Not blocked
64.)
Over 1 MΩ
No dust
Preventive maintenance
Check
Preventive
period
description
Every
year
Exchange
Every
month
Every
Exchange
year
Every
year
Exchange
Every
month
Every
Exchange or
year
repair
Every
Chemical
year
cleaning, etc.
Every
Exchange
year
Every
Exchange
year
Every
year
Exchange
Every
month
Every
Exchange
year
Every
Cleaning
year
Exchange
Fastening
Every
Exchange
year
Every
Exchange or
year
repair
Preventive
period
20,000 hours
10 years
20,000 hours
5 years
5 years
20,000 hours
25,000 hours
20,000 hours
25,000 hours
25,000 hours
25,000 hours
5 years

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents