Water Pipe Installation; Water Pipe Diagram - Samsung AG010KSV Series Installation Manual

Dvm chiller
Table of Contents

Advertisement

Water pipe installation

Water pipe diagram

Install the water system according to the diagram.
Direction of water flow
DVM CHILLER
Water
side heat
02
exchanger
01
Load unit
AHU or
Fan coil
No.
Name
01
Drain plug
02
Coupling
03
Strainer
04
Drain valve
Temperature
05
gauge
Pressure
06
gauge
07
Valve
22
English
Field scope
05
06
09
03
04
Remarks
Make 1/100 ~ 1/200 for drain
to flow by height difference. To
prevent freezing in winter time,
make slope steep and distance of
level side short as possible. Take
appropriate countermeasures
such as drain heater to prevent
freezing in cold region.
Install coupling to allow unit
exchange.
Install strainer at the nearest
place of the product to prevent
foreign materials flow into water
side heat exchanger. (50 Mesh)
Install drain valve to drain water
for service.
It is recommended for checking
ability and operation.
It is recommended for checking
operation status.
Install valves for services such
as flowmeter exchange and
cleaning.
Cleaning and flushing pipe (Install when
08
cleaning)
07
No.
Name
Air vent
08
valve
09
Check valve
10
Pump
11
Flexible joint
Expansion
12
vessel
Expansion vessel
10
11
Remarks
Install air vent valve where
there is a risk of air remaining.
(Auto air valve usable)
Install check valve to prevent
water flowing backward when
pump is stopped.
Install pump which holds amount
for keeping the head loss and
delivering enough water amount
to the product. (Refer to water
flow rate range on page 25.)
It is recommended to prevent
noise and vibration of pump.
To absorb the water volume
change caused by temperature
variation, be sure to install the
expansion vessel.
12
08
04