Samsung AG010KSV Series Installation Manual page 47

Dvm chiller
Table of Contents

Advertisement

No.
Option item
16
AirCool1 (For water law)
17
AirCool2 (For water law)
18
RoomCool1 (For water law)
19
RoomCool2 (For water law)
20
Tcool1 (For water law)
21
Tcool2 (For water law)
22
AirHeat1 (For water law)
23
AirHeat2 (For water law)
24
RoomHeat1 (For water law)
25
RoomHeat2 (For water law)
26
Theat1 (For water law)
27
Theat2 (For water law)
Operation ON/OFF by external
28
contact
29
~
Function expansion available
33
34
Using low temperature function
35
~
Function expansion available
37
Note1)
For options that can be selected by module control and main option, the option value selected for last time will
be saved.
Note2)
Main unit of module when group is not available
Option
Factory
Option
value
default
0 ~ 20
10
30 ~ 40
35
15 ~ 24
20
25 ~ 35
30
-10 ~
15
25
-10 ~
7
25
-20 ~ 5
-10
10 ~ 20
15
15 ~ 24
20
25 ~ 35
30
35 ~ 55
45
35 ~ 55
35
0
0/1
0
1
0
0/1
0
1
Definition
Standard 1 outdoor temperature
for cooling
Standard 2 outdoor temperature
for cooling
Standard 1 room temperature for
cooling
Standard 2 room temperature for
cooling
Standard 1 set temperature for
cooling
Standard 2 set temperature for
cooling
Standard 1 outdoor temperature
for heating
Standard 2 outdoor temperature
for heating
Standard 1 room temperature for
heating
Standard 2 room temperature for
heating
Standard 1 set temperature for
heating
Standard 2 set temperature for
heating
Recognize usual signal
Recognize instant signal
Disuse
Use
Module
control
Setting unit
setting
option
Note1)
Main unit
of group
O
Note2)
Main unit
of group
Note2)
Each unit
47