Electrical wiring work
No.
Name
Set temperature/
room
17-18
temperature
sensor
C-T/B
External
19-20
water outlet
temperature
Usual input: Operate by current status of contact
Instant input: Operate when contact signal changes from OFF to ON / from ON to OFF
Note1)
Value of water outlet set temperature (°C) = 5.625 x Current - 32.5
Heat (Hot water) mode recognizes minimum 25°C (77°F) and maximum 55°C (131°F)
Cool (Cool storage) mode recognizes minimum 5°C (41°F) and maximum 25°C (77°F) (Minimum -10°C (14°F)
when using low temperature function)
Current (mA)
Temperature (°C)
Temperature (°F)
Note2)
Room temperature (°C) = 6.25 x Current - 75
Current (mA)
Temperature (°C)
Temperature (°F)
Note3)
If operation pattern is not standard control, control standard temperature depends on external water outlet
temperature sensor. External water outlet temperature sensor should be installed where can represent the
temperature of water pipe system.
Water outlet temperature (°C) = 6.25 x Current - 55
Current (mA)
Temperature (°C)
Temperature (°F)
Note4)
Operates when input method for quiet function is set as external contact
- If the contact is short, quiet function operates in Cool/Heat mode.
- Quiet function by Module Control operates in Cool mode and night time.
Note5)
Operates when input method for demand function is set as external contact
Note6)
Operates when input method for forced fan function is set as external contact
Note7)
Operates when input method for water law function is set as external contact
Note8)
Main unit of module when group is not available
34
English
Signal
Function
Recognize water outlet set
temperature by external input
Analog
(4 ~ 20 mA)
current
Recognize value of room temperature
sensor (4 ~ 20 mA) when standard for
water law is room temperautre
Recognize external water outlet
Analog
temperature by external temperature
current
sensor (4 ~ 20 mA)
4
6
8
-10.00
1.25
12.50
14.00
34.25
54.50
4
6
8
-50.00
-37.50
-25.00
-58.00
-35.50
-13.00
4
6
8
-30.00
-17.50
-5.00
-22.00
0.50
23.00
Contact On
Contact Off
(Short)
Note1)
-
Note2)
-
Note3)
10
12
14
23.75
35.00
46.25
74.75
95.00
115.25
10
12
14
-12.50
0.00
12.50
9.50
32.00
54.50
10
12
14
7.50
20.00
32.50
45.50
68.00
90.50
Signal
Setting
(Open)
recognition
unit
Main unit
-
Current input
of group
Note8)
Main unit
-
Current input
of group
Note8)
16
18
20
57.50
68.75
80.00
135.50
155.75
176.00
16
18
20
25.00
37.50
50.00
77.00
99.50
122.00
16
18
20
45.00
57.50
70.00
113.00
135.50
158.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents