Base construction and installation

Installation precautions

Connecting the anchor bolt
CAUTION
Tighten the rubber washer to
prevent the bolt connection
part of the DVM CHILLER from
Plastic (rubber)
washer
corroding.
Anchor specification
m
a
Diameter of
Anchor
Size
drill bit (a)
length (b)
ø10
14 (1/2)
75 (3)
(ø3/8)
18
English
Use the anchor bolts and nuts
that is zinc plated or made
of STS material. Regular
anchor bolts or nuts may get
damaged by corrosion.
Unit: mm (inch)
Sleeve
Insertion
Fastening
length (c)
depth
torque
30 N·m
40 (1 1/2)
50 (2)
(22.1 lbf·ft)
Connecting the pipe
If you install the DVM CHILLER on the rooftop,
check the strength and make sure to waterproof the
rooftop.
Construct draining pit around the supporting base
and pay attention to the drainage around the
product. (Condensation or defrost water may form
during product operation.)
If there's any possibility of small animals entering
into the product through pipe outlet, block the outlet.
Water inlet pipe
Water outlet pipe