Connecting the power terminal

Connect the cables to the terminal board with
solderless ring terminals.
Properly connect the cables by using certified and
rated cables and make sure to fix them properly so
that external force is not applied to the terminal.
Use a driver and wrench that can apply the rated
torque when tightening the screws on the terminal
board.
Connect the terminal screws according to the rated
tightening torque.
If the terminal is loose, fire can occur due to arc heat
generation and if the terminal is too tight, terminal
board could get damaged.
Place the part that the sheath of
the power cable is removed inside
the box and connect the protection
tube for power cable to the power
box.
Withdrawing the power cable
through the front
Power cable protection tube
Place the part that the sheath of
the power cable is removed inside
the box and connect the protection
tube for power cable to the power
box.
Withdrawing the power cable
through the side
Connector
Close the cover.
Screw
Tightening torque
5.5~7.3
3 phase (380-415 V) power
M8
(48.7~64.6)
1.2~1.8
M4
(10.6~15.9)
NOTE
When connecting two cables to one terminal,
separate the solderless terminal up and down to
prevent it from getting loose. Place the thin cable
upward and the thick cable downward.
Solderless ring
terminal
Fix the power cable with a cable tie.
CAUTION
When peeling off outer sheath of the power cable,
be careful not to damage the inner sheath of the
cable by using a correct tool.
More than 20 mm (13/16 inch) of power cable or
communication cable of DVM CHILLER should be
inside the electric box.
The installation of communication cable should be
separated from power cable or other communication
cables.
Before connecting the power cable, tighten the
cover of the control box as there might be danger
of electric shock with power supply.
Before checking a compressor or PBA, you must turn
off the power of the product. There is possibility
of power being supplied to the compressor that is
not operating, and therefore there is risk of electric
shock.
Unit : N·m (lbf·in)
cable
Single phase (220-240 V)
power cable
Thick cable
Thin cable