Maintenance

Inspection for normal operation

Item
Have you set the electric conductivity value
properly?
Forced drainage
Is electric conductivity sensor working
properly?
Is auto valve working properly?
Is chilled water corrupted or have floating
particles?
Chilled water and
Is there rust water?
water quality
Is there any red tides?
inspection
Is the concentration of the anti-freeze being
maintained?
Have you set the make-up water supply
value properly?
Chilled water
Is there any excess or deficiency of the
system device
make-up water?
Is the water level within the tank normal for
operation?

Chilled/Heating water flow rate range

If the flow rate of chilled/heating water exceeds optimal range, stop the operation until cause is taken care before re-
start the operation.
Item
Model
Cooling, Heating
68
English
Standard
Rated condition
AG010KSV ✴✴✴
AG015KSV ✴✴✴
90.8 (24.0)
127.2 (33.6)
Number of
inspection
Once a week
Once a month
Once a year (before
winter season)
Once a day
Water flow rate working range
AG010KSV ✴✴✴
59.8 ~ 181.7 (15.8 ~ 48.0) 63.6 ~ 254.4 (16.8 ~ 67.2)
Side effects when
inadequate
Corrosion, water scale or
slime may occur
Corrosion, water scale or
slime may occur
-
Operation problem at the
cooling tower or intensified
water concentration
Unit : LPM (GPM)