ABB TZIDC Manual page 41

Digital positioner for the positioning of pneumatically controlled actuators
Table of Contents

Advertisement

TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B
Error code
Possible cause
Error while processing the measured
values, pointing to an error in the working
data (RAM).
Error during the table processing, pointing
to an error in the working data (RAM).
Error when verifying the checksum of the
configuration data (RAM).
Error in the processor function registers
(RAM).
Internal error.
Impact
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset and the RAM is
reinitialized.
The actuator is moved to the safe position.
After approx. 5 seconds, the positioner is
automatically reset.
Troubleshooting the Instrument
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
If the error persists even after the positioner
has been reset, the device will need to be
returned to the manufacturer for repair.
If the error can be reproduced and occurs in
the same position after resetting, the device
must be returned for repair to the
manufacturer.
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tzidc-200

Table of Contents