Parameter Description Hart - ABB TZIDC Manual

Digital positioner for the positioning of pneumatically controlled actuators
Table of Contents

Advertisement

TZIDC, TZIDC-200 DIGITAL POSITIONER | COI/TZIDC/TZIDC-200-EN REV. B
Parameter description HART®
Parameter Display
Function
P1._
STANDARD
P1.0
ACTUATOR
Actuator type
P1.1
AUTO_ADJ
Auto adjust
P1.2
ADJ_MODE
Auto adjust mode
P1.3
TEST
Test
P1.4
FIND_DEV
Find device
P1.5
EXIT
Return
P2._
SETPOINT
P2.0
MIN_RGE
Min setpoint range
P2.1
MAX_RGE
Max setpoint range
P2.2
CHARACT
Charact. curve
P2.3
ACTION
Valve action
P2.4
SHUT_CLS
Shut-off value 0%
P2.5
SHUT_OPN
Shut off value 100%
P2.6
RAMP UP
Set point ramp, up
P2.7
RAMP DN
Set point ramp, down
P2.8
EXIT
Return
P3._
ACTUATOR
P3.0
MIN_RGE
Min. of stroke range
P3.1
MAX_RGE
Max. of stroke range
P3.2
ZERO_POS
Zero position
P3.3
EXIT
Return
P4._
MESSAGES
P4.0
TIME_OUT
Control time out
P4.1
POS_SW1
Position switch 1
P4.2
POS_SW2
Position switch 2
P4.3
SW1_ACTV
Switchpoint 1 enable
P4.4
SW2_ACTV
Switchpoint 2 enable
P4.5
EXIT
Return
P5._
ALARMS
P5.0
LEAKAGE
Leakage detection
P5.1
SP_RGE
Setpoint rng monitor
P5.2
SENS_RGE
Sens. range monitor
P5.3
CTRLER
Controller monitor
P5.4
TIME_OUT
Control time out
P5.5
STRK_CTR
Stroke counter
P5.6
TRAVEL
Travel counter
P5.7
EXIT
Return
Actuator type
Autoadjust
Automatic adjustment mode
Test
Find device
Return to operating level
Min. setpoint range
Max. setpoint range
Characteristic curve
Direction of action
Shut-off value 0 %
Shut-off value 100%
Setpoint ramp (up)
Setpoint ramp (down)
Return to operating level
Operating range, min.
Operating range, max.
Zero position
Return to operating level
Dead band time limit
Switching point SW1
Switching point SW2
Active direction SW1
Active direction SW2
Return to operating level
Leakage to actuator
Outside the setpoint range
Operating range exceeded
Controller inactive
Dead band time limit
Movement counter
Travel counter
Return to operating level
Possible parameter setting
LINEAR, ROTARY
Function
FULL,STROKE,CTRL_PAR, ZERO_POS, LOCKED
Function
DISABLE, ONE TIME, CONTINOUS
Function
4.0 to 18.4
20.0 to 5.6
LINEAR, 1:25, 1:50, 25:1, 50:1, USERD
DIRECT, REVERSE
OFF, 0.1 to 45.0
55.0 to 100.0, OFF
OFF, 0 to 200
OFF, 0 to 200
Function
0.0 to 90.0
100.0 to 10.0
CLOCKWISE, CTCLOCKWISE
Function
OFF, to 200
0.0 to 100.0
0.0 to 100.0
FALL_BEL, EXCEED
FALL_BEL, EXCEED
Function
ACTIVE, INACTIVE
ACTIVE, INACTIVE
ACTIVE, INACTIVE
ACTIVE, INACTIVE
ACTIVE, INACTIVE
ACTIVE, INACTIVE
ACTIVE, INACTIVE
Function
11
Unit
Factory setting
---
LINEAR
---
---
FULL
---
INACTIVE
---
DISABLE
---
NV_SAVE
mA
4.0
mA
20.0
---
LINEAR
---
DIRECT
%
1.0
%
OFF
---
OFF
---
OFF
---
NV_SAVE
%
0.0
%
100
---
CTCLOCKWISE
---
NV_SAVE
---
OFF
%
0.0
%
100.0
---
FALL_BEL
---
EXCEED
---
NV_SAVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
INACTIVE
---
NV_SAVE