2. Control Functions
Control functions on the module

2.1.12 External thermo operation from external contact

In case of setting the chiller unit to run/stop with the order of an external contact such as that of a (locally supplied) external 
thermo, capacity control function is disabled and operation is performed at 100% load. This function is mainly oriented to 
thermal storage operation.
It is not possible to use this function together with the function to control the number of units.

Setting method
1 Set the local/remote switch (SW2 on PCBa) to remote side. 
2 Connect the forced load operation switch to [24]-[25] of terminal block.
3 The  wiring  side  used  together  by  normal  remote  operation  (air  conditioning  operation)  and  forced  load  operation 
(thermal storage operation) is shown.
Local
Remote
SW2
PBSR2 
(OFF)

Time chart
Forced
load
operation
switch
Chiller 
unit
N O T E
Forced load run/stop from local external contact cannot be performed by pulse signal.
Normal operation order and thermal storage order must be input to the chiller unit separately.
For local external contact orders, ensure a minimum interval of 5 minutes of continuous operation order (5 minutes of
stop time, too).
For the additional wiring, put it separately inside a metallic pipe, or use a shielded wire.
Always operate the air conditioning/thermal storage switch while the chiller unit is stopped.
25
SMGB0097 rev.0 - 07/2015
Remove the wiring between 
5 and 6 if it is connected
5
6
7
Air conditioning
(Thermal storage)
Switch between air conditioning 
and thermal storage
PBSR1 
(OFF)
2 0V
3
ON
OFF
Keep more than 
5 minutes
Run
Stop
24
25
(Thermal 
storage)
(Air conditioning)
SW2
Forced
load
operation
switch
2 0V
3
Keep more than 
5 minutes
2