Hitachi SAMURAI Series Service Manual page 126

Condenserless water chillers
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

4. Troubleshooting
Troubleshooting by alarm code
40-40
Alarm code
Alarm stop reason
 The settings of the DIP relative to the function to control the number of units switch are unrecognisable. 
PCB monitoring position
PCBa (Setting PCB) DSW3-1~3, DSW6-1~3
PCBa (Setting PCB) RSW1
The rotatory switches of PCBA (Setting PCB) 
of master module are correctly set
The DIP switches on PCBA (Setting PCB) of 
each module are correctly set
The H-LINK transmission wiring between 
master module and slave modules is
disconnected or connected wrongly
40-40
Alarm code
Alarm stop reason
Switching of cooling operation order to master module while the system is in operation, when using the function of control 
of Master/Slave group.
Retry indication
No indication
119
SMGB0097 rev.0 - 07/2015
Incorrect Setting of control of Master/Slave group
No
Yes
No
Yes
Yes
No
Wrong operation of Control of Master/Slave group
Switched cooling 
No
operation order during
system operation
Yes
Check PCBc (CPU PCB)
Set the number of 
connected units correctly
Set the DIP switches 
correctly
Check wiring
Check PCBc (CPU PCB)
Check of thermistors
4