Control For Recovery From Power Interruption (Option) - Hitachi SAMURAI Series Service Manual

Condenserless water chillers
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

2. Control Functions
Control functions on the module

2.1.4 Control for recovery from power interruption (Option)

When  this  function  is  enabled,  even  in  the  case  of  power  interruptions  exceeding  2  seconds  in  length,  operation 
restarts  automatically  in  the  operation  mode  as  before  the  power  failure,  once  a  3-minute  guard  has  passed. 
To enable this function, the DIP switch of option C on the settings PCB (PCB

Setting PCB (PCBA)
Power source 
status
Pump operation
order
Chiller unit 
operation status
Compressor
operation status
N O T E
When this function is enabled, recovery upon restoration of the power supply returns to the state before the power
interruption. In case that the chiller unit was in operation before the power interruption, it restarts upon recovery of the
power source. Depending on the situation, this may lead to unintentional automatic startup of the chiller unit.
The control for recovery from power interruption restarts in the same state as before the occurrence of the power
interruption. Therefore, in case that the power interruption occurs while the unit is stopped, it remains stopped even
upon recovery of the power source.
15
SMGB0097 rev.0 - 07/2015
DSW5
Option C
ON
ON
Momentary power failure where rated 
voltage drops by more than 20% with a 
duration between 12ms and 2s
ON
OFF
ON
OFF
ON
OFF
ON
OFF
min
Time guard
) (DSW5-1#) has to be set to ON.
A
1 2 3 4
When the function for recovery 
from power failure is selected 
(In case that this function is 
not selected, it is necessary to 
restart operation)
Power failure exceeding 2 
seconds
Selected from DIP
Time guard
switches
min
2