2. Control Functions
Control of Master/Slave group

2.3.5 Setting items

Water temperature
Addition
Reduction
¦
¡
Outlet water temperature
 Water temperature setting
Sets the temperature in degrees of the outlet water from 
the chiller unit to which the water temperature has to be 
controlled.
Settings  are  performed  at  the  Master  module  LCD 
screen of unit 1. The setting method is the same as with 
the  settings  of  individual  operation.  By  changing  the 
settings of Master module, the settings of slaves 2~8 are 
also changed automatically. 
Refer to
"2.1 Control functions on the module"
¢ Setting temperature difference
Sets the target difference between water inlet and outlet 
temperature to increase the number of units in operation.
£ Temperature range of addition
Sets the range of change of inlet water temperature to 
add  units,  in  case  that  the  difference  of  temperature 
reaches the temperature difference set at ¢.
 Temperature range of reduction
Sets the range of change of inlet temperature to reduce 
units, in case that the difference of temperature reached 
the temperature difference set at ¢.
 Waiting time for effect of addition
Sets the time during which the next addition process is 
prohibited, after having added once (start-up of 1 unit).
Recommended > 3 minutes
 Waiting time for effect of reduction
Sets  the  time  during  which  the  next  reduction  process 
is prohibited, after having reduced once (stop of 1 unit).
Recommended > 3 minutes
47
SMGB0097 rev.0 - 07/2015
Inlet water temperature
§ Number of Units at Startup
Sets  the  number  of  modules  to  be  started  up  upon 
Addition
¥
system start-up.
 Maximum number of operating units
Sets the upper limit of the number of modules that can 
£
be operated at the same time.
¤
© Minimum number of operating units
Sets the minimum number of modules to be operated at 
light load operation.
¢
 Pump operation
Selects batch or individual. 
When  selecting  individual,  pump  operation  order  is 
linked to the run/stop of the module. 
When selecting batch, all the modules which are target 
Time
of  the  control  of  group  (Master/Slave)  during  system 
operation set pump operation order to ON continuously.
 Priority setting
It is possible to set a priority order, when it is necessary 
to operate a certain unit preferentially.
It is possible to set up to 8 steps for priority order.
In  case  that  there  are  multiple  modules  with  the  same 
priority order, they operate in rotation.
Number of the 
Priority setting
The operation time of units with higher priority order
becomes longer.
Settings ¢ to  are performed at the Number of units
setting screen. Refer to
confirmation of operation conditions through the LCD
screen".
1
2
3
4
5
module
1
1
1
2
2
In case that there is a load 
This 3 units are 
exceeding the amount of 3 
operated with the 
units, one unit out of these 4 
maximum priority, with 
is chosen for startup, with a 
a rotation based on
rotation based on operation
operation time
time.
N O T E
"2.3.6 Method for setting and
2
6
8
7
2
2
3
This unit is 