3. Servicing

Cycle components

3.3 Cycle components
C A U T I O N
All operations in the refrigerant cycle require to collect the refrigerant. In those cases proceed as explained
Recovering the refrigerant"
D A N G E R
Turn OFF all the power source switches and ensure that the module is totally stopped before to get inside.
Be careful, some parts and components can be at high temperature.
Access inside the module for servicing can be easily done. The unit is open (except the electrical box) and the inner parts 
are easily accessible.

3.3.1 Compressor removal


When Removing the Compressor
Remove the compressor while completing the following procedures.
1
Before any other operation, collect all refrigerant as described in chapter "3.3.3 Recovering the refrigerant"
2 Remove the bolts on the discharge and suction 
flanges of the compressor.
3 Remove  the  4  bolts  at  the  upper  flange  of  the 
suction pipe.
4 Loosen  the  screw  at  the  metallic  band,  which 
fixes  the  Thermistor.  Softly  pull  the  thermistor 
backwards.
5 Remove all the wiring of the compressor.
64
SMGB0097 rev.0 - 07/2015
Bolts(x4)
Suction pipe
Thermistor THMs)
in"3.3.3
Bolts(x4)
Bolts (x4)
Gasket
Nuts (x4)
Screw