2. Control Functions
Control of Master/Slave group
6 External thermo operation
Functions concentrated in unit 1 (master unit)
By inputting the signal of the following wiring to unit 1, their settings become enabled for all the chiller units in the same 
group.
2-temperature setting
Night shift
Maximum current limitation

2.3.4 Other functions of the control of Master/Slave group

1 About Detachment
Modules stopped by an alarm stop or by a forced stop during operation, as well as modules that have lost communication 
with  Master  module,  become  excluded  from  the  target  of  the  control  of  Master/Slave  group.  (The  same  applies  for 
Master module).
This state is called "Detachment". Also, modules with the local/remote switch in the PCB
detached, too. It is not possible to output operation orders to modules under detachment. (It is possible to operate 
modules in local setting with the Run button in the control panel of the modules as well as with forced operation order)
Also, system operation continues even if a detachment event occurs.
2 About recovery method to system from detachment state
Modules that have been once detached are not subject to the control of Master/Slave group unless performing recovery 
operation.  (However,  modules  that  have  become  detached  because  of  transmission  abnormality  are  recovered 
automatically as soon as transmission is restored ) Perform recovery operation after removing the causes of the Alarm 
and other factors. (Either one of 1 or 2 listed below).
N O T E
Recovery operation: set the local/remote switch in thePCBa (SW2) to remote, and perform the following operation:
• Press down the ON button in the control panel of the module which is under detachment.
• "System Recovery Signal": input from control (according to system conditions).
3 System Operation at Alarm occurrence
Exclude the modules affected by alarm stop, and continue system operation with the rest of the modules. (The same 
applies in case that Master module is stopped by an alarm stop) However, processing of transmission abnormalities 
differs according to the selected control of Master/Slave group. 
Operation of chiller units that have lost communication with Master module.
4 Start-up Order
In case of starting up multiple Modules upon system startup, they are started up sequentially in 10-second intervals.